Title 24 HERS Rater Duct Test and CF-1R CF-2R CF-3R forms
State Certified HERS Raters
HERS TEST - Duct leak testing
Ventura - Los Angeles - San Bernardino and Orange County  Office (805) 551-1050
About our site




Title 24 HVAC Change out requirements
Do I need a Residential Duct Leak Test

Climate zones PDF

The 2016 standard for Duct Testing changed for Residential to the 2019 standard on January 1, 2020.
The change is, if replacing over 75% new ducts it went from
6% leakage to 5% leakage.

For Duct testing information click here.



How the Refrigerant Charge Measurement verification works:

When a new A/C system is installed, the installing contractor performs the refrigerant charge measurement and has an independent, third party HERS rater verify.  This applies when either replacing an existing HVAC unit or installing a new system.  The contractor then fills out the appropriate sections of the standard CF-2R form indicating the proper amount of refrigerant charge.  The HERS rater then verifies the refrigerant charge by attaching their own gauges to the system to measure the refrigerant charge.

The temperature measurement access holes are 5/16 holes that the contractor drills, one in the supply plenum.  Exact locations are specified in the standards.  HVAC installers can attend training seminars sponsored by the state to become familiar with the details of this process.  You can became fairly proficient with the process in about 2 hours of hands on training.

The Saturation temperature measurement sensors are Type K thermocouples that are permanently attached to the evaporator coil and the condenser coil.  The plug on the end of the thermocouple is plugged into a handheld digital thermometer to read the temperature which is then converted into pressure.  The Type K thermocouple must be precisely attached to the indoor coil and the outdoor unit.

The HERS rater then will use their handheld digital thermometer to take eight temperature readings at the system.  The temperature readings are then used to complete a worksheet that determines that a proper refrigerant charge for the system was used.

Cooling Coil Airflow test

Additionally, in Climate Zone’s 10-15, when both the air handler and the duct system are replaced, the HVAC installer must document that the air handler can deliver at least 350 cfm per ton in cooling mode.  This applies to both split and package HVAC units.  The airflow is measured at the return air grill using one of three approved methods:

1. Flow capture hood
2. Flow Grid Device
3. Plenum pressure matching procedure.
4. Temperature split. (Not allowed after 7/1/2014)

A well design duct system will meet the 350 cfm per ton requirement easily, however a duct system that is poorly designed, with many bends that inhibit airflow will fail this test.  This test must be performed by an independent HERS rater.  However the HVAC contractor must first measure the airflow themselves and then fill out the appropriate sections on the CF-2R form.  The HERS rater verifies this with their own airflow test and then will fill out and register the CF-3R form which is then provided to the HVAC contractor, building department and homeowner.

Fan Watt Draw verification

In climate zones 10-15 if the HVAC contractor installs or replaces both the duct system and the air handler the system must meet a Fan Watt Draw standard of 0.58 watts per cfm of airflow for the air handler.  This is a fairly simple test to perform.  The first step is to measure the total system airflow.  Then multiply this number by 0.58 which will give you the maximum watts that the air handler fan can draw.  The final step is to measure the actual fan watt draw using either a plug-in watt meter or a clamp type amp meter and then convert the amps to watts.  An independent HERS rater must verify this test and again fill out a CF-3R to complete this process.

Non-Residential Application:

Duct leakage is prescriptively required in non-residential projects only when all of the following is true:

1. The system is constant volume
2. It serves less than 5000 sq. ft. of conditioned space
3. 25% or more of the duct surface area is located in the outdoors, unconditioned space, a ventilated attic, in a crawl space or where the U-factor of the roof is greater than the U-factor of the ceiling.

Where duct sealing and leakage testing is required, the ducts must be tested by a HERS rater to verify a leakage rate no more than 6% of fan flow.  This applies to new ducts on existing systems AND existing ducts on existing systems that are being either repaired or replaced.

When a entirely new duct system is being installed, and meets the criteria described above, it must meet the leakage rate of no more than 6% of fan flow.  If the new ducts are an extension of an existing duct system the combined system (new and existing ducts) must meet:

1. A leakage rate of less than 15% of fan flow or,
2. A reduction in leakage rate of less than 60% (as compared to the existing ductwork) with all accessible leaks that are visable (with a smoke test) to have been sealed, or
3. All accessible leaks shall be sealed and verified through a visual inspection by a certified HERS rater.

These requirements also apply to cases where existing HVAC equipment is either repaired or replaced.  There is an exception for ducts that are connected to existing ducts that have asbestos insulation sealant.

Another way around the duct sealing and testing requirement is to use the performance compliance method which requires a more complex and detailed analysis of the buildings performance.  If you meet the allowed energy budget for the building without duct sealing and testing then you comply.
Send us an Email - HERS Duct testing
or Email us
Copyright © 2005-2022 https://HomeEnergyRatingService.com  All Rights Reserved
Insured to $1,000,000
My name is Rick we do Hers testing - Duct testing
HERS Rater Duct Test  - Call Office (805) 551-1050 text OK
State Licensed  HERS RATER with  CalCERTS CC2005748 and CHEERS RCN13286
VIDEO-How to pass your HERS test - Duct test