A well design duct system will meet the 350 cfm/ton requirement easily, however a duct system that is poorly designed, with many bends that inhibit airflow will fail this test. This test must be performed by an independent HERS rater. However the HVAC contractor must first measure the airflow themselves and then fill out the appropriate sections on the CF-6R form. The HERS rater verifies this with their own airflow test and then will fill out and register the CF-4R form which is then provided to the HVAC contractor, building department and homeowner.
Fan Watt Draw verification
In climate zones 10-15 if the HVAC contractor installs or replaces both the duct system and the air handler the system must meet a Fan Watt Draw standard of 0.58 watts per cfm of airflow for the air handler. This is a fairly simple test to perform. The first step is to measure the total system airflow. Then multiply this number by 0.58 which will give you the maximum watts that the air handler fan can draw. The final step is to measure the actual fan watt draw using either a plug-in watt meter or a clamp type amp meter and then convert the amps to watts. An independant HERS rater must verify this test and again fill out a CF-4R to complete this process.
Non-Residential Application:
Duct leakage is prescriptively required in non-residential projects only when all of the following is true:
1. The system is constant volume
2. It serves less than 5000 sq. ft. of conditioned space
3. 25% or more of the duct surface area is located in the outdoors, unconditioned space, a ventilated attic, in a crawl space or where the U-factor of the roof is greater than the U-factor of the ceiling.
Where duct sealing and leakage testing is required, the ducts must be tested by a HERS rater to verify a leakage rate no more than 6% of fan flow. This applies to new ducts on existing systems AND existing ducts on existing systems that are being either repaired or replaced.
When a entirely new duct system is being installed, and meets the criteria described above, it must meet the leakage rate of no more than 6% of fan flow. If the new ducts are an extension of an existing duct system the combined system (new and existing ducts) must meet:
1. A leakage rate of less than 15% of fan flow or,
2. A reduction in leakage rate of less than 60% (as compared to the existing ductwork) with all accessible leaks that are visable (with a smoke test) to have been sealed, or
3. All accessible leaks shall be sealed and verified through a visual inspection by a certified HERS rater.
These requirements also apply to cases where existing HVAC equipment is either repaired or replaced. There is an exception for ducts that are connected to existing ducts that have asbestos insulation sealant.
Another way around the duct sealing and testing requirement is to use the performance compliance method which requires a more complex and detailed analysis of the buildings performance. If you meet the allowed energy budget for the building without duct sealing and testing then you comply.